The AA47 Line-Switching Power Pack provides local switching capability to control
loads based on the signal from MSC Series occupancy sensors, independently of any
connection to building control systems. The AA47 routes 120/277 VAC, 60 Hz line
power directly to a Form A relay contact (SPST, normally open) to control a load,
and it generates full-wave, 24 VDC to power up to four MSC sensors (depending on
model). The relay is rated for maximum 15 A tungsten and 20 A ballast loads.
Mounted the AA47 either inside or outside a standard junction box using a 1/2-in.,
threaded EMT nipple. Route power to the sensor(s) using plenum-rated cable.